Clevis Suspension Insulators
ANSI C29.2
¡¡
Figure 1 |
¡¡ ¡¡ ¡¡
Figure 2 |
¡¡
Figure3 |
¡¡
Figure 4 |
ANSI Class |
52-1 |
52-2 |
52-4 |
52-4 high strength |
52-6 |
52-6 high strength |
52-9-A |
52-9-B |
52-10 |
52-10 high strength |
52-12 |
|||
Type of tongue |
With Zinc Sleeve |
With Zinc Sleeve |
With Zinc Sleeve |
With Zinc Sleeve |
With Zinc Sleeve |
With Zinc Sleeve |
With Zinc Sleeve |
With Zinc Sleeve |
With Zinc Sleeve |
With Zinc Sleeve |
With Zinc Sleeve |
|||
No zinc Sleeve |
No zinc Sleeve |
No zinc Sleeve |
No zinc Sleeve |
No zinc Sleeve |
No zinc Sleeve |
No zinc Sleeve |
No zinc Sleeve |
No zinc Sleeve |
No zinc Sleeve |
No zinc Sleeve |
||||
Rated M&E Failing Load(lb.) |
10000 |
15000 |
15000 |
20000 |
25000 |
30000 |
10000 |
10000 |
36000 |
40000 |
50000 |
|||
Fig. No. |
1 |
1 |
2 |
2 |
2 |
2 |
3 |
4 |
2 |
2 |
2 |
|||
Dimensions |
maximum nominal Shell Diameter D(in) |
6-1/2 |
8 |
10 |
10 |
10 |
10 |
4-1/2 |
5-1/2 |
11 |
10 |
12 |
||
Unit Spacing H(in) |
5-1/2 |
5-3/4 |
5-3/4 |
5-3/4 |
5-3/4 |
5 3/4 |
6-1/4 |
6-1/4 |
6-1/2 |
6-1/2 |
7 |
|||
Leakage Distance (in) |
7 |
8 |
11-1/2 |
11-1/2 |
11-1/2 |
11-1/2 |
6-3/4 |
6-3/4 |
11 |
11 |
15 |
|||
a |
7/8 |
11/16 |
11/16 |
11/16 |
11/16 |
11/16 |
7/8 |
7/8 |
13/16 |
13/16 |
15/16 |
|||
b |
1/2 |
1/2 |
1/2 |
1/2 |
1/2 |
1/2 |
1/2 |
1/2 |
3/4 |
3/4 |
7/8 |
|||
c |
5/8 |
5/8 |
5/8 |
5/8 |
5/8 |
5/8 |
5/8 |
5/8 |
3/4 |
3/4 |
7/8 |
|||
d |
11/16 |
11/16 |
11/16 |
11/16 |
11/16 |
11/16 |
11/16 |
11/16 |
11/16 |
11/16 |
3/4 |
|||
e |
11/16 |
11/16 |
11/16 |
11/16 |
11/16 |
11/16 |
11/16 |
11/16 |
13/16 |
13/16 |
15/16 |
|||
Routine Tensile Load (lb.) |
5000 |
7500 |
7500 |
10000 |
12500 |
15000 |
5000 |
5000 |
18000 |
20000 |
25000 |
|||
Impact Strength£¨in-lb.£© |
45 |
50 |
100 |
100 |
100 |
100 |
45 |
45 |
100 |
100 |
100 |
|||
Critical-impulse Flashover Voltage(kV) |
Positive |
100 |
115 |
125 |
125 |
125 |
125 |
100 |
100 |
125 |
140 |
100 |
||
Negative |
100 |
115 |
130 |
130 |
130 |
130 |
90 |
90 |
130 |
140 |
100 |
|||
Low-frequency Flashover Voltage |
Dry |
60 |
65 |
80 |
80 |
80 |
80 |
60 |
60 |
80 |
80 |
80 |
||
Wet |
30 |
35 |
50 |
50 |
50 |
50 |
30 |
30 |
50 |
50 |
50 |
|||
Radio-influence Voltage Data |
Low-frequency Test Voltage, RMS to Ground (kV) |
7.5 |
7.5 |
10 |
10 |
10 |
10 |
7.5 |
7.5 |
10 |
10 |
10 |
||
Max. RIV at 1MHz(¦ÌV) |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
|||
Power-frequency Puncture Voltage (kV) |
80 |
90 |
110 |
110 |
110 |
110 |
80 |
80 |
110 |
110 |
125 |
|||
¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ |
Ball-and-Socket Insulators
ANSI C 29.2
Figure 5
ANSI Class |
52-3 |
52-3 high strength |
52-5 |
52-5 high strength |
52-8 |
52-8 high strength |
52-11 |
||
Type of Ball |
With Zinc Sleeve |
With Zinc Sleeve |
With Zinc Sleeve |
With Zinc Sleeve |
With Zinc Sleeve |
With Zinc Sleeve |
With Zinc Sleeve |
||
No zinc Sleeve |
No zinc Sleeve |
No zinc Sleeve |
No zinc Sleeve |
No zinc Sleeve |
No zinc Sleeve |
No zinc Sleeve |
|||
Rated M&E Failing Load(lb.) |
15000 |
20000 |
25000 |
30000 |
36000 |
40000 |
50000 |
||
Fig. No. | 5 | 5 | 5 | 5 | 5 | 5 | 5 | ||
Dimensions |
maximum nominal Shell Diameter D(in) |
10 |
10 |
10 |
10 |
11-3/4 |
10 |
12 |
|
Unit Spacing H(in) |
5-3/4 |
5-3/4 |
5 -3/4 |
5- 3/4 |
5- 3/4 |
5- 3/4 |
6- 1/8 |
||
Leakage Distance (in) |
11-1/2 |
11-1/2 |
11-1/2 |
11- 1/2 |
12 |
11 |
15 |
||
Routine Tensile Load (lb.) |
7500 |
10000 |
12500 |
15000 |
18000 |
20000 |
25000 |
||
Impact Strength£¨in-lb.£© |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
||
Critical-impulse Flashover Voltage(kV) |
Positive |
125 |
125 |
125 |
125 |
125 |
125 |
140 |
|
Negative |
130 |
130 |
130 |
130 |
130 |
130 |
140 |
||
Low-frequency Flashover Voltage(kV) |
Dry |
80 |
80 |
80 |
80 |
80 |
80 |
80 |
|
Wet |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
||
Radio-influence Voltage Data |
Low-frequency Test Voltage, RMS to Ground (kV) |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
|
Max. RIV at 1MHz(¦ÌV) |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
||
Power-frequency Puncture Voltage (kV) |
110 |
110 |
110 |
110 |
110 |
110 |
125 |
||
Connecting hardware coupling |
B&S Type B |
B&S Type B |
B&S Type J |
B&S Type J |
B&S Type K |
B&S Type K |
B&S Type K |
||
¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ | ¡¡ |
Anti-Pollution Type Ball-and-Socket Insulator
IEC 60373, ANSI 29.2
¡¡
¡¡Figure 6
Cat No. |
No Zinc Sleeve |
24139N |
24190N |
24146N |
24180N |
24311 |
24088H |
24042H |
24050H |
With Zinc Sleeve |
24739N |
24790N |
24746N |
24780N |
24911 |
24688H |
24642H |
24650H |
|
Rated M&E Failing Load (lb.) |
18000 |
25000 |
30000 |
36000 |
50000 |
68000 |
95000 |
120000 |
|
Fig. No. | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | |
Dimensions
|
maximum nominal Shell Diameter D(in) |
10 |
10 |
10 |
12- 5/8 |
12- 5/8 |
12 -5/8 |
13-2/5 |
15-1/3 |
Unit Spacing H(in) |
5- 3/4 |
5- 3/4 |
5- 3/4 |
6 -1/4 |
7 |
7- 2/3 |
8- 1/10 |
9- 9/20 |
|
Leakage Distance (in) |
17- 15/16 |
17- 15/16 |
17 -15/16 |
22- 7/16 |
23- 1/4 |
19- 15/16 |
21- 2/3 |
27 -11/20 |
|
Routine Tensile Load (lb.) |
9000 |
12500 |
15000 |
18000 |
25000 |
34000 |
47500 |
60000 |
|
Impact Strength£¨in-lb.£© |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
|
Critical-impulse Flashover Voltage(kV) |
Positive |
150 |
150 |
150 |
160 |
160 |
150 |
150 |
150 |
Negative |
160 |
160 |
160 |
170 |
170 |
160 |
160 |
160 |
|
Low-frequency Flashover Voltage(kV) |
Dry |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
Wet |
60 |
60 |
60 |
60 |
60 |
60 |
60 |
60 |
|
Radio-influence Voltage Data |
Low-frequency Test Voltage, RMS to Ground (kV) |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
Max. RIV at 1MHz(¦ÌV) |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
|
Power-frequency Puncture Voltage (kV) |
130 |
130 |
130 |
130 |
140 |
140 |
140 |
140 |
|
Connecting hardware coupling |
B&S Type B |
B&S Type J |
B&S Type J |
B&S Type K |
B&S Type K |
IEC 24 |
IEC 28 |
IEC 32 |